Product details

Type designation: SASIL-PL1/N41/AR-H/SKL/NC+NO/ES07

Article number: A1L040100026

Images

a_schaltgeraetekatalog_2009_20090312_057.tif
(Illustration similar)

Description

4-pole Switch disconnector with fuses in accordance to IEC EN60947-3 in a strip design for size 1,with the height 75mm normal switching capacity, for 185mm Busbar distance and busbar thickness 10mm Outgoing strip connection right, manual actuation Number of current transformer: 0 with electronic fuse monitoring ES07 (self supply) and connector strip with NC+NO Version: asymmetrical (standard)

Features

Type:
SASIL-PL1/N41/AR-H/SKL/NC+NO/ES07
Product description:
Lasttrennschalter mit NH-Sicherungen nach IEC/EN 60947-3, VDE 0660 Teil 107;
- mit Leiteranschlüssen rechts, wahlweise unten
- asymmetrischer Gehäuseaufbau
- alle Teile der SASILplus aus halogenfreiem, selbstverlöschendem Material
- Leistenkörper als Träger stromführender Teile aus glasfaserverstärktem Polyester
- Schaltkontakt mit Doppelunterbrechung für hohes Schaltvermögen
- Schaltkontakt mit Vor- und Hauptkontakt für hohe Lebensdauer
- bedienerunabhängiges Schalten
- Zubehör nachrüstbar
Product standard:
IEC/DIN EN60947-3
Cable terminal:
Flat terminal M10
Size:
NH1
Rated operating voltage Ue:
690 V
Conv. free air thermal current with fuse-links Ith:
250 A
Rated frequency:
50 - 60 Hz
Rated isolation voltage Ui:
1,000 V
Total power loss at Ith (without fuse-link) Pv:
68 W
Utilization category 1:
690V - 250A - AC-22B
Utilization category 2:
400V - 250A - AC-23B
Rated impulse voltage Uimp:
8 kV
Rated conditional short-circuit current (distance to grounded parts 0mm) Icc:
55kA (AC690V)
Max. permissible power dissipation per fuse-link:
32 W
Ambient temperature:
-10 up to +55 °C
Type of Actuation:
Independent manual operation
Altitude:
2000 m
Pollution degree:
3
Overvoltage category:
III
Mounting position:
vertical / horizontal
Electrical endurance (switching cycles):
200
Mechanical endurance (total switching cycles):
1,600
Degree of protection:
IP41
configuration:
Asymmetrical
Version:
Outgoing strip connection right (corresponds to connection bottom)
actuation drive:
Manual actuation
Applicable for fuse-links:
NH1
Poles:
4
Switching mode:
4pole switchable
number of current-transformer:
0
wiring of current-transformer:
Current transformer wiring on measuring device and connector strip
plug-in connector for auxiliary wiring:
With connector strip
measuring device:
Without measuring device
auxiliary switch:
1 make and 1 break contact
electronic modules:
Electronic fuse monitoring, self-powered
ETIM - Code:
EC001040
Further developments of our products and technical changes are subject to change. Alterations, errors and errata constitute no claim for damages. Our valid sales terms and delivery conditions are available on our website http://www.jeanmueller.de
Printed at: 27.09.2024 / 03:22