Product details

Type designation: KETO-00-3/60/AOU/R95/ES10

Article number: T501556072

Images

t5_keto-00-3-60-es10_nh-sicherungslasttrennschalter_bearbeitet.png
(Illustration similar)

Description

according to EN60947-3, size NH00 - 160A, 3pole for mounting on 3pole busbar system with 60mm centre-to-centre distance with box clamp R95, max. clamping range: 1,5-95 Al/Cu (Al 95: max. 125A) cable terminal at top or bottom side, at customers option with electronic fuse-monitoring unit ES10

Features

Product Lifecycle:
Active product
Type:
KETO-00-3/60/AOU/R95/ES10
Product standard:
IEC/DIN EN60947-3
Size:
NH00
Rated operating voltage Ue:
500 V
Rated operating current Ie:
160 A
Conv. free air thermal current with fuse-links Ith:
160 A
Rated frequency:
50 - 60 Hz
Rated isolation voltage Ui:
800 V
Total power loss at Ith (without fuse-link) Pv:
14 W
Power loss at 80% Ith (without fuse-link):
9 W
Utilization category 1:
500V - 160A - AC-22B
Utilization category 2:
400V - 160A - AC-23B
Rated impulse voltage Uimp:
8 kV
Rated conditional short-cirquit current Icc:
120 (AC 500V) kA
Rated short-time withstand current (kA):
5
Max. permissible power dissipation per fuse-link:
12 W
Ambient temperature:
-5 up to +55 (>35 Attention derating of rated current required) °C °C
Altitude:
2000 m
Pollution degree:
3
Overvoltage category:
III
Mounting position:
vertical
Electrical endurance (switching cycles):
200
Mechanical endurance (total switching cycles):
1,600
Material properties:
Unterteil:
Temperaturbeständigkeit bis 125°C
Selbsverlöschend nach UL94
Kriechstromfestigkeit CTI 600
Halogenfrei

Schutzabdeckungen, Schaltdeckel:
Temperaturbeständigkeit bis 125°C
Selbsverlöschend nach UL94
Kriechstromfestigkeit CTI 600
Halogenfrei

Sicherungsaufnahmekontakte:
E-Cu, versilbert, fremdbefedert
Degree of protection:
IP2XC
Applicable for fuse-links:
NH000, NH00
Cable terminal:
Frame clamp R95 1,5-95mm² Cu/Al re/rm (Al 95²: max. 125A)
Direction of cable terminal:
variable
Type of installation:
Busbar mounting
Busbar distance:
60 mm
busbar thickness:
  • 5
  • 10
mm
Poles:
3
Special features:
with electronic fuse-monitoring unit ES10
Fuse monitoring:
Electronic Fuse Monitoring Unit ES10
Rated operational voltage:  AC400-500V (+/-10%)
Power supply: Self-powered
Input power: 1,5VA
Overvoltage category: 
  • 230/400V: III (4kV)
  • 500V: II (4kV)
Input resistance: >1k Ohm/V
Temperature range: -5 up to + 55

Relay output: 1NC/1NO
Switching power:
  • AC250V: 1A
  • DC220V: 0,3A
  • DC30V: 2A
Operation indicator: 1 LED green
Alarm indicator: 3 LED (F1, F2, F3) red
Functional test: Test key for relay + LEDs
EMV: IEC 61000-4-5/IEC 61000-4-4
Hight:
195 mm
Width:
106 mm
Width:
106 mm
Depth:
133 mm
ETIM - Code:
EC001040
Further developments of our products and technical changes are subject to change. Alterations, errors and errata constitute no claim for damages. Our valid sales terms and delivery conditions are available on our website http://www.jeanmueller.de
Printed at: 20.09.2024 / 00:38